Scott Trans (Dry Type Transformer) Large Capacity TBS Series

Scott connection transformer JEC-2200/B type (For dedicated battery system Scott transformer, please refer to the SCOTT System)

Scott Transformer (Dry-type Scott Transformer) TBS series Type B (Domestic Use Only) When you want to take a relatively large capacity single-phase load from a three-phase circuit as a balanced load on the three-phase circuit through the transformer connection, this Scott connection method transformer is the most widely used in such cases, for example, for single-phase electric furnaces or single-phase loads for emergency power supplies. ◇Advantages: Balanced load can be applied to the input side three-phase circuit. ◇Disadvantages: The load side (single-phase circuit) must be split into two circuits. However, the two circuits on the load side do not need to be balanced as long as they are below the rated current. ■Standards: JEC-2200 ■Capacity: 1kVA to 30kVA ■Voltage: Please specify your desired voltage for the primary side (P) and secondary side (S). *For battery systems aimed at BCP measures, please refer to the "SCOTT System" (Type H Dry-type, Waterproof Case, with Breaker Box) for dedicated Scott transformers.